LABORATOR ANALIZE APE POTABILE Str. Bogata, nr.1 Tel. 0736663109 |
BULETIN DE ANALIZA
Nr. 16 Data 18.03.2013 Fila nr 1 din 1 |
Cod formular F-LAA-P- 22-01 |
|
Solicitant : CAA Adresa de prelevare : Campia-Turzii, str. Andrei Muresanu, nr.20Natura probei : apa retea distributie Solicitarea analizei: comandă internă □ comanda externa □
|
Data prelevarii : 06.03.2013Prelevator : Szekely Mirela Nr. Recepţie : 1119 Data recepţiei : 06.03.2013 Data efectuarii analizelor : 06-08.03.2013 |
||
INDICATORI ANALIZATI |
UM |
VALORILE OBTINUTE |
VALORILE ADMISE Conform legii 458/2002 |
METODA DE ANALIZA |
Indicatori fizico-chimici |
||||
pH |
Unitati de pH |
7,74(23,1°C) |
6,5 – 9,5 |
SR ISO 10523-12 |
Culoare, gust, miros |
– |
Acceptabila consumatorilor |
Acceptabila consumatorilor |
SR ISO 7887 |
Turbiditate |
FNU |
0,46 |
Max. 5 |
SR EN ISO 7027 |
Conductivitate (250C) |
µS/cm |
895 |
Max. 2500 |
SR EN 27888-97 |
Amoniac |
mg/l |
0,03 |
Max. 0,5 |
SR ISO 7150-1 |
Nitriti |
mg/l |
0,004 |
Max. 0,5 |
SR EN 26777 |
Nitrati |
mg/l |
12,54 |
Max. 50 |
Metoda Merck 1.09713 |
Oxidabilitate |
mgO2/l |
1,12 |
Max. 5 |
SR EN ISO 8467 |
Clor liber |
Mg/l |
0,1 |
0,1- 0,5 |
Metoda Merck 1.00598 |
Indicatori microbiologici |
||||
E.coli |
/ 100 ml |
0 |
0 |
SR EN ISO 9308-1 |
Enterococi |
/ 100 ml |
0 |
0 |
SR EN ISO 7899-2 |
Bacterii coliforme |
/ 100 ml |
0 |
0 |
SR EN ISO 9308-1 |
Interpretare : conform analizelor fizico-chimice si microbiologice, proba de apa este potabila si se incadreaza in prevederile legii 458/2002 si legii 311/2004 privind calitatea apei potabile, pentru indicatorii analizati.
|
DIRECTOR GENERAL REPREZENTANT MANAGEMENT SEF LABORATOR
ALEXANDRU SABAU ANGELICA LASCAU STANCA MARGEANU
Declaraţie: Rezultatele obtinute se refera doar la proba analizata.
Avertisment: Este interzisă reproducerea totala sau parţială a buletinului de analiza fara acordul scris al laboratorului