LABORATOR ANALIZE APE POTABILE Str. Bogata, nr.1 Tel. 0736663109 |
BULETIN DE ANALIZA
Nr. 45 Data 27.06.2013 Fila nr 1 din 1 |
Cod formular F-LAA-P- 22-01 |
|
|
Solicitant : CAA Adresa de prelevare : Turda, str. Eminescu, CantinaNatura probei : apa retea distributie Solicitarea analizei: comandă internă □ comanda externa □
|
Data prelevarii : 25.06.2013Prelevator : Ghig Lucian Nr. Recepţie : 2874 Data recepţiei : 25.06.2013 Data efectuarii analizelor : 25-27.06.2013 |
||
|
INDICATORI ANALIZATI |
UM |
VALORILE OBTINUTE |
VALORILE ADMISE Conform legii 458/2002 |
METODA DE ANALIZA |
|
Indicatori fizico-chimici |
||||
|
pH (temperatura) |
Unitati de pH |
7,54(23,7°C) |
6,5 – 9,5 |
SR ISO 10523/2012 |
|
Turbiditate |
FNU |
1,3 |
Max. 5 |
SR EN ISO 7027/2001 |
|
Conductivitate (250C) |
µS/cm |
399 |
Max. 2500 |
SR EN 27888/1997 |
|
Amoniac |
mg/l |
0,012 |
Max. 0,5 |
SR ISO 7150-1/2001 |
|
Nitriti |
mg/l |
0,003 |
Max. 0,5 |
SR EN 26777/2006 |
|
Nitrati |
mg/l |
4,7 |
Max. 50 |
Metoda Merck 1.09713 |
|
Oxidabilitate |
mgO2/l |
0,32 |
Max. 5 |
SR EN ISO 8467/2001 |
|
Clor liber |
mg/l |
0,2 |
0,1- 0,5 |
Metoda Merck 1.00598 |
|
Indicatori microbiologici |
||||
|
E.coli |
/ 100 ml |
0 |
0 |
SR EN ISO 9308-1/2004 |
|
Enterococi |
/ 100 ml |
0 |
0 |
SR EN ISO 7899-2/2002 |
|
Bacterii coliforme |
/ 100 ml |
0 |
0 |
SR EN ISO 9308-1/2004 |
|
Interpretare : conform analizelor fizico-chimice si microbiologice efectuate, proba de apa este potabila si se incadreaza in prevederile legii 458/2002 si legii 311/2004 privind calitatea apei potabile, pentru indicatorii analizati.
|
||||
DIRECTOR GENERAL REPREZENTANT MANAGEMENT SEF LABORATOR
ALEXANDRU SABAU ANGELICA LASCAU STANCA MARGEANU
Declaraţie: Rezultatele obtinute se refera doar la proba analizata.
Avertisment: Este interzisă reproducerea totala sau parţială a buletinului de analiza fara acordul scris al laboratorului