LABORATOR ANALIZE APE POTABILE Str. Bogata, nr.1 Tel. 0736663109 |
BULETIN DE ANALIZA
Nr. 50 Data 19.07.2013 Fila nr 1 din 1 |
Cod formular F-LAA-P- 22-01 |
|
Solicitant : Adresa de prelevare : Turda , str. Andrei Muresanu, SpitalNatura probei : apa retea distributie Solicitarea analizei: comandă internă □ comanda externa □
|
Data prelevarii : 15.07.2013Prelevator : Ghig Lucian Nr. Recepţie : 3158 Data recepţiei : 15.07.2013 Data efectuarii analizelor : 15-17.07.2013 |
||
INDICATORI ANALIZATI |
UM |
VALORILE OBTINUTE |
VALORILE ADMISE Conform legii 458/2002 |
METODA DE ANA |
Indicatori fizico-chimici |
||||
pH (temperatura) |
Unitati de pH |
7,53(23,3°C) |
6,5 – 9,5 |
SR ISO 10523/2012 |
Turbiditate |
FNU |
0,84 |
Max. 5 |
SR EN ISO 7027/2001 |
Conductivitate (250C) |
µS/cm |
399 |
Max. 2500 |
SR EN 27888/1997 |
Amoniac |
mg/l |
˂ MDL |
Max. 0,5 |
SR ISO 7150-1/2001 |
Nitriti |
mg/l |
0,006 |
Max. 0,5 |
SR EN 26777/2006 |
Nitrati |
mg/l |
11,7 |
Max. 50 |
Metoda Merck 1.09713 |
Oxidabilitate |
mgO2/l |
0,48 |
Max. 5 |
SR EN ISO 8467/2001 |
Clor liber |
mg/l |
0,19 |
0,1- 0,5 |
Metoda Merck 1.00598 |
Indicatori microbiologici |
||||
E.coli |
/ 100 ml |
0 |
0 |
SR EN ISO 9308-1/2004 |
Enterococi |
/ 100 ml |
0 |
0 |
SR EN ISO 7899-2/2002 |
Bacterii coliforme |
/ 100 ml |
0 |
0 |
SR EN ISO 9308-1/2004 |
Interpretare : conform analizelor fizico-chimice si microbiologice efectuate, proba de apa este potabila si se incadreaza in prevederile legii 458/2002 si legii 311/2004 privind calitatea apei potabile, pentru indicatorii analizati.
|
NOTA – MDL (limita de detectie a metodei in cazul amoniului este 0,002)
DIRECTOR GENERAL REPREZENTANT MANAGEMENT SEF LABORATOR
CRISTIAN OCTAVIAN MATEI ANGELICA LASCAU STANCA MARGEANU
Declaraţie: Rezultatele obtinute se refera doar la proba analizata.
Avertisment: Este interzisă reproducerea totala sau parţială a buletinului de analiza fara acordul scris al laboratorului